Pump selection and pipe sizing for a 480-bed student residence

Size the rising main, select a transfer pump and a top-floor booster, and cut the pumping bill for a six-storey student residence that runs out of water every morning.

Core EngineeringMechanical Engineering
6 Guided Steps24h Internship TierSubmit: Demand and head-loss workbook + system curve with pump operating point + booster selection + energy cost comparison + short report with a schematicVerified CertificateAI Rubric Graded
Program Overview

Industry project · for Kestrel Campus Housing, a student-accommodation operator with a 480-bed residence in Pretoria and a twin building planned in Pune

Kestrel's Pretoria residence has 480 beds over six floors. Municipal water fills a 60 m³ ground-level sump. A single 5.5 kW pump lifts it to a 40 m³ roof tank, and gravity feeds the floors from there. Both the sump and the roof tank are standard because city supply is cut for hours at a time, and the Pune twin will face the same intermittent supply.

Three things go wrong. Between 06:30 and 08:00 the roof tank empties faster than the pump refills it, and the top two floors get a trickle. The pump has burnt out twice in 18 months, and the maintenance team suspects it runs far from its best efficiency point. The electricity bill for pumping is R4,100 a month, which the finance manager thinks is too high.

The facts you have: - the roof tank outlet is 22.5 m above the sump water level; - the rising main is 68 m of 50 mm HDPE with six bends and two valves; - the top-floor showers are only 3.2 m below the roof tank outlet and need at least 1.0 bar to work well; - residents use about 150 L per person per day, and 45% of that happens in the morning peak.

Your job is to: - calculate the demand and peak flow; - size the rising main and the distribution pipes; - draw the system curve and select a pump from a real manufacturer curve; - size a small booster set for floors 5 and 6; - work out the running cost in rand and rupees.

You need no site visit. Everything is done by hand calculation and a spreadsheet, with an optional network check in the free EPANET software.

Done looks like a pump that refills the tank in under 3 hours, works near its best efficiency point, gives top-floor pressure of at least 1.0 bar, and costs less to run than today.

Water demand estimationPipe friction and minor lossesSystem curvesPump selectionNPSH checkEnergy cost calculation
What you submit

Demand and head-loss workbook + system curve with pump operating point + booster selection + energy cost comparison + short report with a schematic

Stack: Spreadsheet, Manufacturer pump curves (any public catalogue), EPANET (optional), Python with Matplotlib (optional)

How it is graded
  • Correct demand and losses30

    Daily demand, peak flow, pipe friction and fitting losses are calculated correctly with every assumption stated.

  • Right pump, right point30

    The chosen pump meets the refill target, its operating point is within 80–110% of best efficiency flow, and NPSH is checked.

  • Top-floor pressure solved20

    A booster or other solution gives at least 1.0 bar at the top-floor showers, with its duty point stated.

  • Cost and report20

    Monthly running cost is compared with today in rand and rupees, and a short report with a schematic explains the change.

Pass 60% · Merit 75% · Distinction 90%

Learning Outcomes
Estimate building water demand and peak flow
calculate pipe friction and fitting losses
draw a system curve and read a pump curve
check NPSH and best efficiency point
compare running costs
Target Audience

Engineering Students

Diploma, B.Tech, B.E., BCA, MCA, or M.Tech students seeking practical experience.

Aspiring Developers

Developers who want to build proof-of-work capstone projects for tech resumes.

Job Seekers

Graduates looking for AI-evaluated code review & verified industry credentials.