Heat loss and cold-climate heat-pump sizing for a Winnipeg townhouse
Calculate the design heat loss of a typical townhouse at −33 °C, size a cold-climate heat pump with backup heat, and compare yearly running cost with the old gas furnace.
Industry project · for Prairie Hearth Housing Co-operative, a 24-home housing co-op in Winnipeg, Manitoba, replacing ageing gas furnaces
Prairie Hearth owns 24 townhouses built in 1978. Each home is two storeys, 112 m² of heated floor over a heated basement, with a 22-year-old gas furnace that is reaching the end of its life. The co-op board wants to replace all 24 with cold-climate air-source heat pumps over two summers, using federal and provincial rebates. A sister co-op in Minneapolis is watching to see if it works.
The board has two worries. A contractor quoted a 5-ton heat pump per home "to be safe", which seems large. And some members fear the heat pumps will not cope at −33 °C, so their electric backup heat will run all winter and bills will rise.
You will work out the answer for one typical end-unit: - set the design conditions for Winnipeg from climate data; - calculate heat loss through walls, windows, roof, basement, air leakage and ventilation; - size a heat pump from a manufacturer-style capacity table and find the balance point where backup heat starts; - estimate yearly energy use and cost with a temperature-bin method, comparing gas and the heat pump; - check whether air sealing or attic insulation first would let a smaller heat pump do the job.
The home's construction is in task 1. You need no site visit. All the work is done in a spreadsheet, with optional Python for the bin calculation.
Done looks like a design heat loss in kW, a recommended heat-pump size in tons with a reason, the share of yearly heat that backup provides, and a yearly cost comparison in Canadian dollars. The board wants a one-page answer they can read at the next members' meeting.
Design basis + heat-loss workbook + balance-point chart + annual energy and cost comparison + upgrade options note + one-page board summary
Stack: Spreadsheet, Python with pandas (optional), Climate data tables, Manufacturer-style heat-pump performance table (given)
- Correct heat loss35
Conduction, basement, infiltration and ventilation losses are calculated for every element at the design temperature, with RSI and U-values shown.
- Sensible sizing25
The heat pump is sized against design load and capacity at low temperature, the balance point is found, and the 5-ton quote is assessed.
- Seasonal energy25
A bin method gives yearly heat-pump, backup and gas energy and cost, with the share of heat from backup stated.
- Board summary15
A one-page summary gives the recommended size, the yearly cost difference and what to do first, in plain language.
Pass 60% · Merit 75% · Distinction 90%