Electrical design for a cold-climate heat-pump retrofit
Check whether a 100 A house service can take a cold-climate heat pump, backup heat and an EV charger, do the CEC load calculation, size the circuits and give the owners a clear choice: upgrade or load management.
Industry project · for Prairie Comfort Renovations, a Winnipeg contractor converting a 1970s bungalow from a gas furnace to a cold-climate heat pump
The Harper family own a 1,250 ft² bungalow in Winnipeg with a finished basement. They want to replace their 80% gas furnace and gas water heater with a cold-climate air-source heat pump, electric backup heat and a heat-pump water heater, and they plan to buy an electric car next year. Prairie Comfort has sold them the mechanical side. The electrical side is now your job.
What you know: - Winnipeg's winter design temperature is about −33 °C, and the house loses about 11.5 kW of heat at that temperature. - The existing service is 100 A at 120/240 V, and the 24-space panel has 3 spaces free. The house already has a 12 kW electric range and a 5 kW dryer. - The proposed heat pump is a 3-ton cold-climate unit. Its nameplate gives a minimum circuit ampacity of 25 A and a maximum overcurrent protection of 40 A at 240 V. The backup is a 10 kW electric strip heater in the air handler. - The EV charger they want is a 7.2 kW Level 2 unit on a 40 A circuit. - The utility quoted about C$4,500 and 10 weeks for a 200 A service upgrade, and the panel would also need replacing.
The homeowners want to know three things: does everything fit on 100 A, what will it cost to run compared with gas, and what is the cheapest safe way to do it. Prairie Comfort needs a design its electrician can permit and install.
You will size the heat pump against the heat loss and find the balance point, survey the panel, do the single-dwelling load calculation under the Canadian Electrical Code, compare a service upgrade with a load-management device, size every new circuit, draw the panel schedule and single-line diagram, and estimate running cost. All of this is done on paper or in a spreadsheet, with manufacturer data and the code.
Done looks like a design pack for the electrician and a two-page report for the Harpers that they can read at the kitchen table.
Heat-loss and balance-point sheet + service load calculation + options comparison + circuit sizing table + panel schedule and SLD + two-page homeowner report
Stack: Spreadsheet, Canadian Electrical Code (or BS 7671 for UK students), Heat-pump and charger datasheets, draw.io or any CAD tool
- Correct heating analysis20
Heat loss is scaled across outdoor temperatures, the heat pump's capacity curve is used to find the balance point, and backup heat is justified.
- Correct service load calculation25
The single-dwelling calculation follows the code method step by step with every demand factor shown, and the result is compared with 100 A.
- Sound options comparison20
Service upgrade and load management are compared on cost, time, comfort and code compliance, with a clear recommendation.
- Installable design25
Every new circuit has a breaker, conductor size and voltage drop check from nameplate data, and the panel schedule and SLD are complete.
- Clear homeowner report10
The Harpers can understand what is proposed, what it costs, what it saves or costs to run, and what changes in winter.
Pass 60% · Merit 75% · Distinction 90%